Unit developed and manufactured by AGUILERA ELECTRONICA according to UNE EN54-2 norm to monitor fires, the technical signals and other parameterchanges that occur in mobile booths and similar premises.
Formed by:
- Stabilized power supply, powered at 230 V with input protection, outputs at 27 and 12 V CC and battery charger.
- Monitored loop that controls one area of fire detectors and fire switches, with signaling of: 1st level of fire, 2nd level, breakdown and service.
- Loop monitored for the automatic fire extinction, programmable to release the extinguishing agent, with the 1st or 2nd level of fire.
- Relays: about fire, supervised general breakdown, air conditioning pause and repetition of the external alarms, 1 and 14.
- Control of 14 inputs, depending on the model, individually selectable via normally open or closed contact, which are transmitted by sub D37-pin connectors(2A relay outputs, voltage free by contact individually selectable, open or closed).
- Dimensions: 375 x 280 x 130mm.
Unit developed and manufactured by AGUILERA ELECTRONICA according to UNE EN54-2 norm to monitor fires, the technical signals and other parameterchanges that occur in mobile booths and similar premises.
Formed by:
- Stabilized power supply, powered at 230 V with input protection, outputs at 27 and 12 V CC and battery charger.
- Monitored loop that controls one area of fire detectors and fire switches, with signaling of: 1st level of fire, 2nd level, breakdown and service.
- Loop monitored for the automatic fire extinction, programmable to release the extinguishing agent, with the 1st or 2nd level of fire.
- Relays: about fire, supervised general breakdown, air conditioning pause and repetition of the external alarms, 1 and 14.
- Control of 30 inputs, depending on the model, individually selectable via normally open or closed contact, which are transmitted by sub D37-pin connectors(2A relay outputs, voltage free by contact individually selectable, open or closed).
- Dimensions: 375 x 280 x 130mm.
The central unit of alarms, AE/AX30TRI model is a central fire control unit and is repeating the external alarms for three different operators.
Basically it consists of:
- Power supply and battery charger.
- Fire detection loop.
- Control circuit for automatic extinction that provides for a monitored output in orderto activate a solenoid valve.
- Output by relay (24 V).
- Output of 12 VDC (500 mA.) for various uses external to the central unit.
- Control of 30 external alarm inputs, normally open or normally closed, selectableby a switch (outputs of the 30 alarms via potential-free relays, normally open orclosed, selectable by a selector switch).
- For the first 14 outputs, plus fire alarm and general fault alarm it has three Sub-D connectors of 37 pins, to be used independently by each operator. This informationis repeated simultaneously on all three connectors.
- For the remaining 16 outputs is available only one Sub-D connector of 37 pins.
- Repetition through two switched relays of 2 A, with voltage free inputs1 and 30.
- Control of one FIRE output and one GENERAL FAULT output, both normally closed, through the first 3 Sub-D connectors of 37 pins.
- 2 A voltage free relays switched for:
- Fire alarm.
- General fault alarm (normally energized).
- Ventilation stop, selectable with fire level 1 or level 2.
- Optical and audible signals, as well as the necessary controls for the managementof the installation.
Metallic micro-processed central cabinets, according to EN-54, parts 2 and 4.
They have:
- 2 conventional detection loops with an active end of line.
- Control to access levels by key.
- 2 monitored exits for evacuation.
- Fire relay (general alarm).
- Auxiliary output of 24 V CC.
- 6-key keyboard for proper handling.
- Test zones mode.
- Separate power on/off, for detection zones and evacuation zones.
- 10 independent LEDs for alarm indications.
- They need one unique 12V/7Ah battery.
- They perform continuous monitoring of the entire system.
- Dimensions AE/C5-2M: 200 x 290 x 80. Weight: 2.8 Kg.
Micro-processed central cabinets, nicely designed, manufactured in ABS, accordingto EN54, parts 2 and 4.
They have:
- 2 conventional detection loops with an active end of line.
- Control to access levels by key.
- 2 monitored exits for evacuation.
- Fire relay (general alarm).
- General Fault Relay.
- Auxiliary output of 24 V CC.
- 6-key keyboard for proper handling.
- “”Test monitored areas”” mode.
- They need one unique 12V / 7Ah battery.
- They perform continuous monitoring of the entire system.
- Dimensions: 340 x 290 x 100. Weight: 2.5 Kg.
Central control with the same features as the AE/C5-2P central, but with 4 conventional detection zones, CE certificates, according to EN-54, parts 2 and 4. Dimensions AE/C5-4M: 320 x 220 x 80. Weight: 2.8 Kg.
Central with the same features as the AE/C5-2P central, but with four conventional detection zones.CE certificates according to EN 54, parts 2 and 4
Modular, micro-processed, central unit manufactured according to EN 54-2 and EN 54-4.
- Modular capacity between 8, 12 and 16 zones of conventional detection with anactive end of line.
- Monitored exits for evacuation.
- Fault and fire detector relay.
- Test monitored areas mode.
- Control keys and status indicating LEDs.
- Capacity for a 12V /18Ah battery.
- Dimensions: 462 X 345 X 120.
The 12-zone control panel can be requested by ordering an AE/C5-8-16 central unit and a 4-zone AE/C5-MZ4 card.
The 16-zone central control unit is requested by ordering an AE/C5-8-16 central unit and two 4-zone AE/C5-MZ4 cards.
De similares características que la central AE/C5-4P pero con 8 zonas de detección convencional. Dispone de selección de zona de pulsadores o zona de detectores, retardo de las salidas y conexión al módulo de relés AE/C5-R8. Dimensiones 340X290X100. Permite su control remoto mediante el módulo AE/C5-IDC y el software de telecontrol AGE44.
Module of 8 remote relays for the AE/C5-8-16 central unit. It has free contacts Normally Open or Normally Closed, individually selectable through a jumper.The relays are individually activated in case of zone alarm.
The module requires external 24 V CC power supply. The connection is via 4 or 6 wires (if they feed from the central panel).
- Maximum distance from the central unit: 1000 m.
- Maximum number of modules: 2.
Developed and manufactured by Aguilera Electronica under EN12094-1.
Characteristics:
- 2 monitored detection zones.
- Operating mode, programmable as:
- Double detection:Two alarms in one zone.
- Crossed detection: One alarm in every zone.
- Mixed: Two alarms in the panel.
- Monitored detection zone for trigger extinction button.
- Monitored entry zone for extinction pause button.
- Buttons for extinguishing the fire and pausing extinction built into the panel.
- 2 independent monitored inputs for pressure monitoring or control of weighingand flow control.
- Monitored output for evacuation and for fire extinguishing poster.
- Mode selection key: automatic, manual or unarmed.
- Display indicating the time remaining for the discharge.
- Output time before extinction programmable between 0 and 60 seconds.
- Optional relays in order to repeat the central unit states.
- Dimensions: 320 x 272 x 125 mm.• It can receive 2 batteries of 12V/7Ah.