Referencia: AE/FL-T2

Unit for flame detector test

Unit for testing the range of flame detectors ( UV, UV / IR,UV / IR ², IR³, IR ²,IR). This test unit has been designed to generate a wide range of signals of optical output.

Portable equipment with NiCd rechargeable battery. Selection of the type of optical output wanted (constant, intermittent lighting, flickering similar to flames). Lead time between tests is 30 seconds. Range 3 metres. Tests in intrinsically safe areas can be carried out (consult the manual for this application).

Referencia: AE/IS-Z

Galvanic isolators 2 detection zones

Single-channel galvanic isolator (AE/IS-ZG )
Compatible with intrinsically safe equipments of the IS series.
Classified II1G EEXia IIC (T4) in BASEEFA: BAS 98 ATEX 7343.
Voltage Vo 25.2 V, Current Io 93 mA, Power Po 585 mW.
Double-channel galvanic isolator (AE/IS-Z).

AE/IS-ZG. Galvanic isolators 1 detection zone
Single-channel galvanic isolator (AE/IS-ZG )
Compatible with intrinsically safe equipments of the IS series.
Classified II1G EEXia IIC (T4) in BASEEFA: BAS 98 ATEX 7343.
Voltage Vo 25.2 V, Current Io 93 mA, Power Po 585 mW.
Double-channel galvanic isolator (AE/IS-Z).

AE/IS-ZS. Galvanic isolators sirens/focus
Single-channel galvanic isolator (AE/IS-ZG )
Compatible with intrinsically safe equipments of the IS series.
Classified II1G EEXia IIC (T4) in BASEEFA: BAS 98 ATEX 7343.
Voltage Vo 25.2 V, Current Io 93 mA, Power Po 585 mW.
Double-channel galvanic isolator (AE/IS-Z).

Referencia: AE/FL-IR2

IR2 Flame detector with double sensor

Dual infrared flame detector, mounted in zinc alloy casing. Its micro-processor technology allows it to work with different levels of flame intensity and operates normally under adverse conditions. The detector sensitivity can be adjusted in accordance with the EN 54-10 regulation.

  • Certified EN54-10 .
  • Supply voltage 14 – 30 VDC .
  • Current supplied 3/9, 4/8/14, 4-20, 8-20 mA .
  • Field of view 90° min. Conical. Spectral response (IR) 1 to 2.7 microm.
  • Operation temperature -10°C to 55°C, Storage temperature -20°C to 65°C.
  • Non-condensing relative humidity 95%.
  • Protection range IP65.
  • Weight 2 kg
Referencia: AE/FL-IR2EX

IR2 Exd ATEX Flame detector

Dual infrared flame detector mounted in flameproof casing Its micro-processor technology allows it to work with different levels of flame intensity and operates normally under adverse conditions. The detector sensitivity can be adjusted in accordance with EN54-10.

  • Supply voltage 14 – 30 VDC .
  • Current supplied 3/9, 4/8/14, 4-20, 8-20 mA .
  • Field of view 90° min. Conical. Spectral response (IR) 1 to 2.7 microm.
  • Operation temperature -10°C to 55°C, Storage temperature -20°C to 65°C.
  • Non-condensing relative humidity 95%.
  • Protection range IP66
  • Weight 2.5 kg
  • IEC EEx d IIC T6
Referencia: AE/FL-IR3

IR3 Flame detector

IR³ flame detector with fire-resistant cover. Highly sensitive micro-processor which allows it to operate through smoke, oil, dust or water vapour. Sensitivity adjustable according to the EN54-10.

  • Supply voltage 14 – 30 VDC .
  • Current supplied 3/9, 4/8/14, 4-20, 8-20 mA .
  • Field of view 90° min. Conical
  • Responds to a wave length ranging from 0.75 to 2.7μm emitted by all type of fire.
  • Operation temperature -10°C to 55°C, Storage temperature -20°C to 65°C.
  • Non-condensing relative humidity 95%.
  • Protection range IP65
  • Weight 2 kg. Dimensions : 108 x 142 x 82 mm
Referencia: AE/FL-IR3EX

IR3EX Flame detector

IR³ flame detector with fire-resistant cover. Highly sensitive micro-processormwhich allows it to operate through smoke, oil, dust or water vapour. Sensitivity adjustable according to the EN54-10.

Responds to a wave length ranging from 0.75 to 2.7μm emitted by all type of fire. Detects non-visible gas fires such as hydrogen gas fires. IR³ detectors.

Allows to discriminate between flames and false radiation sources of the IR, as the combination of filters and signal processing prevents from false alarms.

  • Supply voltage 14 – 30 VDC .
  • Current supplied 3/9, 4/8/14, 4-20, 8-20 mA .
  • Field of view 90° min. Conical.
  • Spectral response (IR) 1 to 2.7 microm.
  • Operation temperature -10°C to 55°C, Storage temperature -20°C to 65°C
  • Non-condensing relative humidity 95%.
  • Protection range IP66
  • Weight 2.5 kg; Dimensions: 146 x 150 x 137 mm
  • IEC EEx d IIC T6 Certified”
Referencia: AE/FL-UVIR2

UV/ IR Double technology flame detector

Flame detector with double technology infrared sensors (IR) and ultraviolet (UV: 185 a 260 nm). Detection cone 90º and detention distance up to 45 metres. Low consumption (8mA). A relay output is incorporated. Programmable sensitivity. Filters and analysis through micro-processor for false alarm elimination.

  • Spectral response in the infrared: 1 at 2,7um.
  • Power supply 14-30Vcc.
  • Consumption: 20mA.
  • Certified IEC EEx d IIC T6.
Referencia: AE/FL-UVIR2EX

Exd ATEX Double technology flame detector

Flame detector with double technology infrared sensors (IR) and ultraviolet (UV: 185 a 260 nm). Detection cone 90º and detention distance up to 45 metres.

  • Low consumption (8mA). A relay output is incorporated. Programmable  sensitivity.
  • Filters and analysis through micro-processor for false alarm elimination.
  • Spectral response in the infrared: 1 at 2,7um.
  • Power supply 14-30Vcc. Consumption: 20mA.
  • Zinc alloy casing with IP66-protection.”