TITANUS MICRO·SENS® has been developed to monitor small and medium size of installations & premises. However, it provides many different features and operating options, such as:
- A version with ROOM·IDENT allows the localization of fire with the precision of asingle smoke detector point.
- A version for use in freezer chambers allows the use in applications below – 40 ºC.
- The compatibility with Ethernet networks through this device allows for integration with external monitoring systems.
With a TITANUS MICRO·SENS® system can be replaced up to 8 single smoke detectors. For that reason duct lengths of up to 50 m will be provided, whether required A, or B, or C, or not, according to EN 54-20.
Designed for applications which require fire detection individually for a given area, for small to medium enclosures of up to 400 m2, equipments, up to 5 contiguous premises (hotel rooms …), autonomous equipments (wind turbines, transformers …)
Specifications:
- Energy supply: 24V CC (14 – 30 V CC)
- Max. power consumption at rest: 105 mA
- Max. power consumption of alarm: 110-140 mA
- Dimensions: 140x222x70 mm
- Weight: 850 to 895 gr
- Temperature interval: -20ºC to +60ºC
- Humidity: from 10% to 95% without condensation.
- Two levels of alarm (alarm and pre-alarm).
- Relay switch free of output voltage for alarm and general fault alarm.
- Class of protection: up to IP 54.
- EN 54-20 certificates, classes A, B, C, nº 0786-CPD-20322.
- VdS Approval nº G 206004
REFERENCE | SENSITIVITY | LEVEL INDICATOR | ROOM IDENT. |
AETM-50I | 0.5% | NO | SI |
AETM-50B | 0.5% | SI | NO |
AETM-50BI | 0.5% | SI | SI |
AETM-10 | 0.1% | NO | NO |
AAETM-10I | 0.1% | NO | SI |
AETM-10B | 0.1% | SI | NO |
AETM-10BI | 0.1% | SI | SI |
Microsens for a refrigerated environment
REFERENCE | SENSITIVITY | LEVEL INDICATOR |
AETM-F50 | 0.5% | NO |
AETM-F50B | 0.5% | SI |
AETM-F10 | 0.1% | NO |
AETM-F10B | 0.1% | SI |
TITANUS PRO·SENS® has been developed for a broad range of applications.
The high modularity of the system offers an economical solution tailored to individual customer needs.
It offers the following options:
- Connection to one or two detector modules. With just one device we can monitor two areas, or even double detection in the same area (by using the adapter in “Y” AET-P01109255 mode).
- From 1 to 3 levels of alarm (warning, pre-alarm and alarm) with relays switched free of voltage, depending on the model, for each detector module.
- Fault Detector Relay.
- Ethernet network connection, using AET / IT network card (not for TP1 models).
- Connection to Aguilera Electronica´s algorithmic loop through the card AE/SAIT.
- Specific version for refrigerated zones, which can be used in applications up to -40ºC.
- Silent version, with a noise level of 23 dB (A).
Specifications:
- Energy supply: 24V CC (14 – 30)
- Dimensions: 200x292x113 mm
- Temperature interval: -20ºC to +60ºC
- Humidity: from 10% to 95% without condensation.
- Certificates EN 54-20, classes A, B, C, nº 0786-CPD-20685.
- VdS Approval nº G 202064
- Max. number of aspiration openings: 32
- Max. duct length: 300 m
- Consumption at rest: 200 mA
- Maximum power consumption in alarm: 210 mA””
REFERENCE | SENSITIVITY |
AETP1-50 | 0.5% |
AETP1-10 | 0.1% |
AETP1-01 | 0.015% |
REFERENCE | SENSITIVITY |
AETP1-F50 | 0.5% |
AETP1-F10 | 0.1% |
AETP1-F01 | 0.015% |
- Max. number of aspiration openings 64 (2 x 32)
- Max. duct length: 560 m (2 x 280)
- Consumption at rest: 220 mA
- Maximum power consumption in alarm: 240 mA
REFERENCE | MODULE 1 | MODULE 2 |
AETP1-2-50 | 0.5% | 0.5% |
AETP1-2-1050 | 0.1% | 0.5% |
AETP1-2-10 | 0.1% | 0.1% |
AETP1-2-0150 | 0.15% | 0.5% |
AETP1-2-0110 | 0.15% | 0.1% |
AETP1-2-01 | 0.15% | 0.15% |
REFERENCE | MODULE 1 | MODULE 2 |
AETP1-F2-50 | 0.5% | 0.5% |
AETP1-F2-1050 | 0.1% | 0.5% |
AETP1-F2-101 | 0.1% | 0.1% |
AETP1-F2-0150 | 0.15% | 0.5% |
AETP1-F2-0110 | 0.15% | 0.1% |
AETP1-F2-01 | 0.15% | 0.15% |
Titanus Prosens TP1 type – 2 detection modules for refrigerated environment
REFERENCE | MODULE 1 | MODULE 2 |
AETP1-2-D5050 | 0.5% | 0.5% |
AETP1-2-D1050 | 0.1% | 0.5% |
AETP1-2-D0150 | 0.15% | 0.5% |
AETP1-2-D0110 | 0.015% | 0.1% |
- Max. number of aspiration openings 32
- Max. duct length: 300 m
- Consumption at rest: 210 mA
- Maximum power consumption in alarm: 220 mA
REFERENCE | SENSITIVITY |
AETP4-50 | 0.5% |
AETP4-10 | 0.1% |
AETP4-01 | 0.015% |
- Max. number of aspiration openings: 64 (2 x 32)
- Max. duct length: 560 m (2 x 280)
- Consumption at rest: 240 mA
- Maximum power consumption in alarm: 250 mA
REFERENCE | SENSITIVITY |
ARTP4-F50 | 0.5% |
ARTP4-F10 | 0.1% |
ARTP4-F01 | 0.015% |
- Max. number of aspiration openings: 64 (2 x 32)
- Max. duct length: 560 m (2 x 280)
- Consumption at rest 240 mA
- Maximum power consumption in alarm: 250 mA
SENSITIVITY OF ALARM RESPONSE |
REFERENCE | MODULE 1 | MODULE 2 |
AETP4-2-50. | 0.5% | 0.5% |
AETP4-2-1050 | 0.1% | 0.5% |
AETP4-2-10 | 0.1% | 0.1% |
AETP4-2-0150 | 0.015% | 0.5% |
AETP4-2-0110 | 0.015% | 0.1% |
AETP4-2-01 | 0.015% | 0.015% |
- Max. number of aspiration openings: 64 (2 x 32)
- Max. duct length: 560 m (2 x 280)
- Consumption at rest: 240 mA
- Maximum power consumption in alarm: 250 mA
SENSITIVITY OF ALARM RESPONSE |
REFERENCE | MODULE 1 | MODULE 2 |
AETP4-2-D5050 | 0.5% | 0.5% |
AETP4-2-D1050. | 0.1% | 0.5% |
AETP4-2-D0150 | 0.015% | 0.5% |
AETP4-2-D0110 | 0.015% | 0.1% |
- Max. number of aspiration openings: 32)
- Max. duct length: 560 m (2 x 280)
- Consumption at rest: 240 mA
- Maximum power consumption in alarm: 250 mA
SENSITIVITY OF ALARM RESPONSE |
REFERENCE | MODULE 1 | MODULE 2 |
AETP4-F2-50 | 0.5% | 0.5% |
AETP4-F2-1050 | 0.1% | 0.5% |
AETP4-F2-10 | 0.1% | 0.1% |
AETP4-F2-0150 | 0.015% | 0.5% |
AETP4-F2-0110 | 0.015% | 0.1% |
AETP4-F2-01 | 0.015% | 0.015% |
- Max. number of aspiration openings: 32
- Max. duct length: 300 m
- Consumption at rest: 210 mA
- Maximum power consumption in alarm: 220 mA
REFERENCE | SENSITIVITY |
AETP5-50 | 0.5% |
AETP5-10 | 0.1% |
AETP5-01 | 0.015% |
- Max. number of aspiration openings: 32
- Max. duct length: 300 m
- Consumption at rest: 210 mA
- Maximum power consumption in alarm: 220 mA
REFERENCE | SENSITIVITY |
AETP5-F50 | 0.5% |
AETP5-F10 | 0.1% |
AETP5-F01 | 0.015% |
- Max. number of aspiration openings: 64 (2 x 32)/li>
- Max. duct length: 560 m (2 x 280)/li>
- Consumption at rest: 240 mA/li>
- Maximum power consumption in alarm: 250 mA
SENSITIVITY OF ALARM RESPONSE |
REFERENCE | MODULE 1 | MODULE 2 |
AETP5-2-50 | 0.5% | 0.5% |
AETP5-2-1050 | 0.1% | 0.5% |
AETP5-2-10 | 0.1% | 0.1% |
AETP5-2-0150 | 0.015% | 0.5% |
AETP5-2-0110 | 0.015% | 0.1% |
AETP5-2-01 | 0.015% | 0.015% |
- Max. number of aspiration openings: 64 (2 x 32)
- Max. duct length: 560 m (2 x 280)
- Consumption at rest: 240 mA
- Maximum power consumption in alarm: 250 mA
SENSITIVITY OF ALARM RESPONSE |
REFERENCE | MODULE 1 | MODULE 2 |
AETP5-2-D1050 | 0.1% | 0.5% |
AETP5-2-D0150 | 0.015% | 0.5% |
AETP5-2-D0110 | 0.015% | 0.1% |
- Max. number of aspiration openings: 64 (2 x 32)
- Max. duct length: 560 m (2 x 280)
- Consumption at rest: 240 mA
- Maximum power consumption in alarm: 250 mA
SENSITIVITY OF ALARM RESPONSE |
REFERENCE | MODULE 1 | MODULE 2 |
AETP5-F2-50. | 0.5% | 0.5% |
AETP5-F2-1050 | 0.1% | 0.5% |
AETP5-F2-10 | 0.1% | 0.1% |
AETP5-F2-0150 | 0.015% | 0.5% |
AETP5-F2-0110 | 0.015% | 0.1% |
AETP5-F2-01 | 0.015% | 0.015% |
TITANUS RACK·SENS® modular systems fire protection for the control of electronic cabinets of 19 inch format.
The system meets the highest requirements regarding security in the IT sector and for the first time, it provides the advantages of the improved TITANUS systems for smoke detection by air sampling, for the control of 19″ equipment.
TITANUS RACK·SENS® is available upon request by the customer, as:
- 19″ module / 1HU for earliest possible detection of fires.
- 19″ module / 2 HU for earliest possible detection of fires with fire extinguishing integrated. Its many different versions and extension accessories allow for its individual adaptation to customer’s requirements.
They provide:
- 2 alarm levels
- 6 frontal Leds indicating the status: service, disconnection, shot, pre-alarm, alarm and fault.
- Relays free of output voltage for alarm and fault.
- Optional 10-digit bar graph that keeps the user informed about the current smoke level.
- Output for remote indicator
- Certificates EN54-20 nº: 0786-CPD-20322• VdS Approval nº: G206004
AETR2-C. TITANUS RACK-SENS® 2 heights (1 cylinder)
AETR2-C. TITANUS RACK-SENS® 2 heights (2 cylinders)
REFERENCE | DETECTORS | SENSITIVITY | LEVEL INDICATOR |
AETR-50 | 1 | 0.5% | NO |
AETR-50B | 1 | 0.5% | SI |
AETR-10 | 1 | 0.1% | NO |
AETM-10 | 1 | 0.1% | SI |
REFERENCE | DETECTORS | SENSOR DETECTOR 1 | SENSOR DETECTOR 2 | IND. DE LED | CYLINDRES |
AETR2-1D | 1 | 0.5% | | NO | 1 |
AETR2-1DB | 1 | 0.5% | | SI | 1 |
AETR2-1D2C | 1 | 0.5% | | NO | 2 |
AETR2-1D2CB | 1 | 0.5% | | SI | 2 |
AETR2-2D | 2 | 0.5% | 0.1% | NO | 1 |
AETR2-2DB | 2 | 0.5% | 0.1% | SI | 1 |
AETR2-2D2C | 2 | 0.5% | 0.1% | NO | 2 |
AETR2-2D2CB | 2 | 0.5% | 0.1% | SI | 2 |
Specifically developed for applications with the highest detection standards. The system shows its special ability to detect pyrolysis gases, released during thermal processes,much before anyone can even speak of a “”fire””.
TITANUS SUPER·SENS® is a high sensitivity device for detecting smoke by takingair samples, for use in special applications such as telecommunication areas, CPD data centres and for monitoring clean-air rooms.
It offers numerous features, functions and operation options:
- 3 alarm trigger points (warning, pre-alarm and alarm) with relays switched free ofvoltage
- Fault Detector Relay.
- 10-digit bar graph that keeps the user informed about the current smoke level presentin the monitored area.
- Ethernet network connection, using an AET/ ITR network card.
- Galvanic version for superior protection of areas with a corrosive atmosphere.
This variant ensures a longer life span in the presence of corrosive gases.
TITANUS SUPER·SENS® coverage goes far beyond the classification EN 54-20. The alarm’s sensitivity can be set, depending on the version, up to 600 times more sensitive than is necessary for reaching class A.
For that there will be pipe lengths of up to 200 m, regardless of what type of class, A,B or C is required, according to EN 54-20.
Specifications:
- Energy supply: 24V CC (14 – 30)
- Max. power consumption at rest: 245 mA
- Max. power consumption of alarm: 320 mA
- Max. nº of aspiration openings: 24
- Maximum duct length: 200 m
- Dimensions: 240 x 366 x 132 mm
- Temperature interval: -20ºC to +60ºC
- Humidity: from 10% to 95% without condensation.
- Sensitivity of alarm response: 0.006% obs/m
- Certificates: EN 54-20, classes A, B, C, nº 0786-CPD-20781
- VdS Approval nº: G201035″
The TITANUS TOP·SENS® is a high sensitivity device for smoke detection by aspiration,with many operating features and options:
- Connection to one or two detector modules. With just one device we can monitor two areas, or even double detection in the same area (by using the adapter in V mode)
- 3 alarm trigger points (warning, pre-alarm and alarm) with relays switched free of voltage, for each detector module.
- Fault Detector Relay.
- 10-digit bar graph for each detector module, which keeps the user informed about the current smoke level that is present in the monitored area.
- Ethernet network connection, by using AET / IT network card.
- Connection to Aguilera Electronica´s algorithmic loop through the AE/SA-IT card.
- Specific version for refrigerated zones, used in applications of up to -40ºC.
- Silent version, with a noise level of 23 dB (A).
Specifications:
- Energy supply: 24V CC (14 – 30 V CC)
- Temperature interval: -20ºC to +60ºC
- Class of protection: IP 20 (IP 52 is optional)
- Dimensions: 200 x 292 x 113 mm
- Humidity: from 10% to 95% without condensation
- Dimensions: 200 x 292 x 113 mm
- Certificates EN 54-20, classes A, B, C, number 0786-CPD-20685.
- VdS Approval nº: G202064
REFERENCE | SENSITIVITY |
AETT-50 | 0.5% |
AETT-10 | 0.1% |
AETT-01 | 0.015% |
REFERENCE | SENSITIVITY |
AETT-F50 | 0.5% |
AETT-F10 | 0.1% |
AETT-F01 | 0.015% |
SENSITIVITY OF ALARM RESPONSE |
REFERENCE | MODULE 1 | MODULE 2 |
AETT-2-50 | 0.5% | 0.5% |
AETT-2-1050 | 0.1% | 0.5% |
AETT-2-10 | 0.1% | 0.1% |
AETT-2-0150 | 0.015% | 0.5% |
AETT-2-0110 | 0.015% | 0.1% |
AETT-2-01 | 0.015% | 0.015% |
SENSITIVITY OF ALARM RESPONSE |
REFERENCE | MODULE 1 | MODULE 2 |
AETT-F2-50 | 0.5% | 0.5% |
AETT-F2-1050 | 0.1% | 0.5% |
AETT-F2-10 | 0.1% | 0.1% |
AETT-F2-0150 | 0.015% | 0.5% |
AETT-F2-0110 | 0.015% | 0.1% |
AETT-F2-01 | 0.015% | 0.015% |
SENSITIVITY OF ALARM RESPONSE |
REFERENCE | MODULE 1 | MODULE 2 |
AETT-2-D5050 | 0.5% | 0.5% |
AETT-2-D1050 | 0.1% | 0.5% |
AETT-2-D0150 | 0.015% | 0.5% |
AETT-2-D0110 | 0.015% | 0.1% |