Referencia: AETM

AETM Titanus Microsens

TITANUS MICRO·SENS® has been developed to monitor small and medium size of installations & premises. However, it provides many different features and operating options, such as:

  • A version with ROOM·IDENT allows the localization of fire with the precision of asingle smoke detector point.
  • A version for use in freezer chambers allows the use in applications below – 40 ºC.
  • The compatibility with Ethernet networks through this device allows for integration with external monitoring systems.

With a TITANUS MICRO·SENS® system can be replaced up to 8 single smoke detectors. For that reason duct lengths of up to 50 m will be provided, whether required A, or B, or C, or not, according to EN 54-20.

Designed for applications which require fire detection individually for a given area, for small to medium enclosures of up to 400 m2, equipments, up to 5 contiguous premises (hotel rooms …), autonomous equipments (wind turbines, transformers …)

Specifications:

  • Energy supply: 24V CC (14 – 30 V CC)
  • Max. power consumption at rest: 105 mA
  • Max. power consumption of alarm: 110-140 mA
  • Dimensions: 140x222x70 mm
  • Weight: 850 to 895 gr
  • Temperature interval: -20ºC to +60ºC
  • Humidity: from 10% to 95% without condensation.
  • Two levels of alarm (alarm and pre-alarm).
  • Relay switch free of output voltage for alarm and general fault alarm.
  • Class of protection: up to IP 54.
  • EN 54-20 certificates, classes A, B, C, nº 0786-CPD-20322.
  • VdS Approval nº G 206004
REFERENCESENSITIVITYLEVEL INDICATORROOM IDENT.
AETM-50I0.5%NOSI
AETM-50B0.5%SINO
AETM-50BI0.5%SISI
AETM-100.1%NONO
AAETM-10I0.1%NOSI
AETM-10B0.1%SINO
AETM-10BI0.1%SISI

Microsens for a refrigerated environment

REFERENCESENSITIVITYLEVEL INDICATOR
AETM-F500.5%NO
AETM-F50B0.5%SI
AETM-F100.1%NO
AETM-F10B0.1%SI