Referencia: AETS

TITANUS SUPER-SENS®

Specifically developed for applications with the highest detection standards. The system shows its special ability to detect pyrolysis gases, released during thermal processes,much before anyone can even speak of a “”fire””.

TITANUS SUPER·SENS® is a high sensitivity device for detecting smoke by takingair samples, for use in special applications such as telecommunication areas, CPD data centres and for monitoring clean-air rooms.

It offers numerous features, functions and operation options:

  • 3 alarm trigger points (warning, pre-alarm and alarm) with relays switched free ofvoltage
  • Fault Detector Relay.
  • 10-digit bar graph that keeps the user informed about the current smoke level presentin the monitored area.
  • Ethernet network connection, using an AET/ ITR network card.
  • Galvanic version for superior protection of areas with a corrosive atmosphere.

This variant ensures a longer life span in the presence of corrosive gases.

TITANUS SUPER·SENS® coverage goes far beyond the classification EN 54-20. The alarm’s sensitivity can be set, depending on the version, up to 600 times more sensitive than is necessary for reaching class A.

For that there will be pipe lengths of up to 200 m, regardless of what type of class, A,B or C is required, according to EN 54-20.

Specifications:

  • Energy supply: 24V CC (14 – 30)
  • Max. power consumption at rest: 245 mA
  • Max. power consumption of alarm: 320 mA
  • Max. nº of aspiration openings: 24
  • Maximum duct length: 200 m
  • Dimensions: 240 x 366 x 132 mm
  • Temperature interval: -20ºC to +60ºC
  • Humidity: from 10% to 95% without condensation.
  • Sensitivity of alarm response: 0.006% obs/m
  • Certificates: EN 54-20, classes A, B, C, nº 0786-CPD-20781
  • VdS Approval nº: G201035″