Push button designed according to EN12094-3 norm, in order to block the ignition of a system of extinction, in blue color, for interior use, serigraphically printed with thetext: HOLD.
Equipped with: Micro-switch, verification, test system with reset key, transparent methacrylate protection cover, normally open contacts (NO), common C, normallyclosed (NC) contacts and calibrated plastic sheet, so that it locks and does not break.
Introduced in an ABS box of 98X98X50 mm.
Manual call point designed according to EN12094-3 norm, to trigger the ignition of anextinguishing system, in yellow colour, for interior use, serigraphically printed with thetext: RELEASE.
Equipped with: Micro-switch, verification test system with reset key, transparent methacrylate protection cover, normally open contacts (NO), common C, normallyclosed (NC) contacts and calibrated plastic sheet, so that it locks and does not break.
Introduced in an ABS box of 98X98X50 mm”
Evacuation manual call point, designed for its installation in emergency exits.
Greencolor. Interior use.
Equipped with: Microswitch, verification, test system with reset key, transparent methacrylate protection cover, normally open contacts (NO), common C, normallyclosed (NC) contacts and calibrated plastic sheet, so that it locks and does not break.
Introduced in an ABS box of 98X98X50 mm
Pack with 8 plastic seals, useful for the AE/V-PB2, AE/V-PD2 and AE/V-PE manual call points
Developed and manufactured by Aguilera Electronica under EN 54-11 norm.
Equipped with: micro-switch, alarm LED with a self-test LED, verification system with reset key, calibrated plastic sheet, so that it locks and it will not break.
- Push button protective cap.
- Mounted in an ABS case.
- CE Certificate issued by LPCB.
- Dimensions: 98 X 95X 39 mm
Conventional alarm manual call point suitable for outdoor use, IP65 according to EN 54-11 norm.
Equipped with a microswitch, with a load resistance of 470 ohms or 680ohms, verification system with reset key and LED signal alarm.
Allows the assembly of a calibrated plastic sheet, so that it locks and will not break, or of a breakable glasssheet, supplied both of them.
ABS case of 85x85x58 mm. CE certificate according to DPC. LPCB certificate.
Protection: IP 65
Conventional alarm manual call point, water resistant with an IP67 protection, certified according to EN54-11 norm. It has two independent switches with voltage free contacts,valid for connecting the switch to conventional or algorithmic systems through the corresponding module. In its interior it can accommodate the miniature module of 1 input. It incorporates calibrated plastic sheet, so that it locks and does not break, averification system with a reset key and a visible image of alarm, confirming its activation.
- Dimensions: 119mm x128mm x 62mm
- Operating temperature: – 20ºC to + 65ºC
Manufactured from strong, transparent polycarbonate that resists temperatures between -40 º C and + 49ºC.
Easy installation.
Warning and assistance system for disable persons. A 2-wire system consisting of a double-handle warning pushbutton, acoustic and light indicator, reset pushbutton and power supply. Can be integrated in the fire central units of the SA series of Aguilera Electrónica through an algorithmic module.
Certified according to EN 54-4 norm and with maximum output current of 12A, respectively.
Manufactured according to the European standards and directives: DBT, CEM, DEEE 2002/96 CE and RoHS 2002/95CE.
They incorporate the following functions:
- Two power supply outputs independently protected.
- Real-time monitoring of the complete state of the system: network data interface,power supply charger, battery and protections.
- Temperature compensation: a system of temperature compensation of the batterythat permits keeping the characteristics of the batteries´ charge in the entire rangeof temperature use.
- Product designed and dimensioned to function at nominal rated power, during 24hours.
- Capacity for batteries of up to 48Ah.
- Dimensions: 408x408x224mm
Short-circuitable dedicated power supply of 24V CC / 5A and 2A manufactured according to the EN 54-4 norm.
Dual voltage 230/115 VAC, 50/60Hz. Equipped with luminous indications on the generalstate of power supply, status and battery charge and of the output fuses as of EN 54-4 norm.
They have 2 independent outputs protected against short circuits.
Batteries:
- AE/FL-2A has the capacity for 2 batteries 12V/17Ah.
- Dimensions: 272x320x125mm.
Short-circuitable dedicated power supply of 24V CC / 5A and 2A manufactured according to the EN 54-4 norm.
Dual voltage 230/115 VAC, 50/60Hz. Equipped with luminous indications on the generalstate of power supply, status and battery charge and of the output fuses as of EN 54-4 norm.
They have 2 independent outputs protected against short circuits.
Batteries:
- AE/FL-5A has the capacity for 2 batteries 12V/17Ah.
- Dimensions: 440x390x100 mm
Certified according to EN 54-4 norm and with maximum output current of 8A.
Manufactured according to the European standards and directives: DBT, CEM, DEEE 2002/96 CE and RoHS 2002/95CE.
They incorporate the following functions:
- Two power supply outputs independently protected
- Real-time monitoring of the complete state of the system: network data interface,power supply charger, battery and protections.
- Temperature compensation: a system of temperature compensation of the batterythat permits keeping the characteristics of the batteries´ charge in the entire rangeof temperature use.
- Product designed and dimensioned to function at nominal rated power, during 24hours.
- Capacity for batteries of up to 48Ah.
- Dimensions: 408x408x224mm
EN 1155 Certified.Traction force: 100 Kg / 980 N
- Power consumption: 100 mA 24 Vdc.
- Protection: IP40
Retainer of 100 Kg/980N for the floor with an extendable arm of 15 to 18 cm, with atraction plate, push button release and 2 protection diodes.
- EN 1155 certified. Protection: IP40
- Power consumption: 45mA 24Vdc