Referencia: AE/V-PB2

Hold manual call point

Push button designed according to EN12094-3 norm, in order to block the ignition of a system of extinction, in blue color, for interior use, serigraphically printed with thetext: HOLD.
Equipped with: Micro-switch, verification, test system with reset key, transparent methacrylate protection cover, normally open contacts (NO), common C, normallyclosed (NC) contacts and calibrated plastic sheet, so that it locks and does not break.

Introduced in an ABS box of 98X98X50 mm.

Referencia: AE/V-PD2

Release manual call point

Manual call point designed according to EN12094-3 norm, to trigger the ignition of anextinguishing system, in yellow colour, for interior use, serigraphically printed with thetext: RELEASE.

Equipped with: Micro-switch, verification test system with reset key, transparent methacrylate protection cover, normally open contacts (NO), common C, normallyclosed (NC) contacts and calibrated plastic sheet, so that it locks and does not break.

Introduced in an ABS box of 98X98X50 mm”

Referencia: AE/V-PE

Emergency manual call point

Evacuation manual call point, designed for its installation in emergency exits.
Greencolor. Interior use.

Equipped with: Microswitch, verification, test system with reset key, transparent methacrylate protection cover, normally open contacts (NO), common C, normallyclosed (NC) contacts and calibrated plastic sheet, so that it locks and does not break.

Introduced in an ABS box of 98X98X50 mm

Referencia: AE/V-PSAT

Manual call point with self-test

Developed and manufactured by Aguilera Electronica under EN 54-11 norm.

Equipped with: micro-switch, alarm LED with a self-test LED, verification system with reset key, calibrated plastic sheet, so that it locks and it will not break.

  • Push button protective cap.
  • Mounted in an ABS case.
  • CE Certificate issued by LPCB.
  • Dimensions: 98 X 95X 39 mm
Referencia: AE/V-PSIP

Outdoor manual call point

Conventional alarm manual call point suitable for outdoor use, IP65 according to EN 54-11 norm.

Equipped with a microswitch, with a load resistance of 470 ohms or 680ohms, verification system with reset key and LED signal alarm.

Allows the assembly of a calibrated plastic sheet, so that it locks and will not break, or of a breakable glasssheet, supplied both of them.

ABS case of 85x85x58 mm. CE certificate according to DPC. LPCB certificate.
Protection: IP 65

Referencia: AE/V-PSIP67

Outdoor IP67 manual call point

Conventional alarm manual call point, water resistant with an IP67 protection, certified according to EN54-11 norm. It has two independent switches with voltage free contacts,valid for connecting the switch to conventional or algorithmic systems through the corresponding module. In its interior it can accommodate the miniature module of 1 input. It incorporates calibrated plastic sheet, so that it locks and does not break, averification system with a reset key and a visible image of alarm, confirming its activation.

  • Dimensions: 119mm x128mm x 62mm
  • Operating temperature: – 20ºC to + 65ºC
Referencia: AE/DDA

Assistance system for disabled persons

Warning and assistance system for disable persons. A 2-wire system consisting of a double-handle warning pushbutton, acoustic and light indicator, reset pushbutton and power supply. Can be integrated in the fire central units of the SA series of Aguilera Electrónica through an algorithmic module.

Referencia: AE/FL-12A

High capacity power supply units (12A)

Certified according to EN 54-4 norm and with maximum output current of 12A, respectively.
Manufactured according to the European standards and directives: DBT, CEM, DEEE 2002/96 CE and RoHS 2002/95CE.

They incorporate the following functions:

  • Two power supply outputs independently protected.
  • Real-time monitoring of the complete state of the system: network data interface,power supply charger, battery and protections.
  • Temperature compensation: a system of temperature compensation of the batterythat permits keeping the characteristics of the batteries´ charge in the entire rangeof temperature use.
  • Product designed and dimensioned to function at nominal rated power, during 24hours.
  • Capacity for batteries of up to 48Ah.
  • Dimensions: 408x408x224mm
Referencia: AE/FL-2A

Switched power supply 24 V 2 A

Short-circuitable dedicated power supply of 24V CC / 5A and 2A manufactured according to the EN 54-4 norm.

Dual voltage 230/115 VAC, 50/60Hz. Equipped with luminous indications on the generalstate of power supply, status and battery charge and of the output fuses as of EN 54-4 norm.
They have 2 independent outputs protected against short circuits.

Batteries:

  • AE/FL-2A has the capacity for 2 batteries 12V/17Ah.
  • Dimensions: 272x320x125mm.
Referencia: AE/FL-5A

Switched power supply 24 V 5 A

Short-circuitable dedicated power supply of 24V CC / 5A and 2A manufactured according to the EN 54-4 norm.

Dual voltage 230/115 VAC, 50/60Hz. Equipped with luminous indications on the generalstate of power supply, status and battery charge and of the output fuses as of EN 54-4 norm.

They have 2 independent outputs protected against short circuits.

Batteries:

  • AE/FL-5A has the capacity for 2 batteries 12V/17Ah.
  • Dimensions: 440x390x100 mm
Referencia: AE/FL-8A

High capacity power supply units (8A)

Certified according to EN 54-4 norm and with maximum output current of 8A.
Manufactured according to the European standards and directives: DBT, CEM, DEEE 2002/96 CE and RoHS 2002/95CE.

They incorporate the following functions:

  • Two power supply outputs independently protected
  • Real-time monitoring of the complete state of the system: network data interface,power supply charger, battery and protections.
  • Temperature compensation: a system of temperature compensation of the batterythat permits keeping the characteristics of the batteries´ charge in the entire rangeof temperature use.
  • Product designed and dimensioned to function at nominal rated power, during 24hours.
  • Capacity for batteries of up to 48Ah.
  • Dimensions: 408x408x224mm