Referencia: AE/SA-CTL

Card of 2 loops of 2 wires

Control unit micro-processed of two analogical loops manufactured by AGUILERAELECTRONICA. The capacity of each loop is that of 125 devices each, to which thedetectors, push buttons, modules for manoeuvres, for control and any other elementsthat make up the installation, all connect, with a capacity
for a total control of 250devices.

It has indicator lights for the control, proper operation and the communications betweenthe central unit& the devices.

Referencia: AE/SA-C1

Algorithmic control panel of 1 loop

Panel for fire control with capacity for 1 loop of 125 equipments each,to which
the detectors, switches, modules for manoeuvres, for control and otherelements
that make up the installation, all connect.

  • Switched power supply of 27.2 Vdc at 2 A.
  • Emergency battery charger with capacity for receiving two 12V /7Ah batteries.
  • Dimensions: Height: 274 – Width: 322 – Depth: 123 mm
Referencia: AE/SA-C2

Algorithmic control panel of 2 loops

Panel for fire control with a capacity for a AE/SA-CTL of 2 loops of 125 equipments each, to which the detectors, switches, modules for manoeuvres, for controland other elements that make up the installation, all connect and with a capacity tocontrol 250 devices.

  • Switched power supply of 27.2 Vdc at 4 A.
  • Emergency battery charger, where the central unit has the capacity to receive in its interior, two 12V/ 7Ah batteries.
  • Dimensions: Height: 410 – Width: 310 – Depth: 120 mm
Referencia: AE/SA-C8

Algorithmic control panel of 8 loops

“Panels for fire control with bus for connecting with 1 to 4 cardsAE /SA-CTL.
Each card controls two bidirectional algorithmic loops, with a capacityfor 125
equipments each, to which the detectors, switches, modules for manoeuvres,
forcontrol and other elements that make up the installation, all connect.
The control panel’s capacity to control equipment is up to 1000 devices and
dependingon the type it can mean controlling more than 3000 independent
points. For every 250devices the central unit is equipped with an independent
microprocessor.
Independently switched power supply of 27.2 Vdc at 4 A.
Emergency battery charger, where the central unit has capacity for receiving
in itsinterior, two 12V/17Ah batteries.
Dimension: Height: 500 – Width: 390 – Depth: 145 mm”

Referencia: AE/SA-PX2

Extinguishing control panel

Developed and manufactured by Aguilera Electronica under Norm UNE EN12094-1.

Characteristics:

  • 2 monitored detection zones.
  • Operating mode, programmable as:
    • Double detection: Two alarms in one zone.
    • Crossed detection: One alarm in every zone.
    • Mixed: Two alarms in the panel.
  • Monitored detection zone for push button to trigger the fire extinction.
  • Monitored entry zone for an extinction pause button.
  • Buttons for extinguishing the fire and pausing extinction built into the panel.
  • 2 independent monitored inputs for pressure monitoring or control of weighing and flow control.
  • Monitored output for evacuation and for fire extinguishing poster.
  • Mode selection key: automatic, manual or unarmed.
  • Display indicating the time remaining for the discharge.
  • Output time before extinction programmable between 0 and 60 seconds.
  • Can be integrated into the algorithmic system.
  • Optional relays in order to repeat the states of the central unit.
  • Dimensions: 320 x 272 x 125 mm.
  • It can receive 2 batteries of 12V/7Ah.
  • Equipped with a micro-processed card that keeps permanently informed thecentralalgorithmic unit regarding its status.