Stainless steel connection click with closing arc.
Weight: 10g

Stainless steel connection click with closing arc.
Weight: 10g
“J” shape connection bracket with fire Rawplug proof, nut and cable flange.
Weight: 100g
Input module for connection status, galvanically disconnected, for controlled desactivating of the differential evaluation during determinate process step.
Sensors cable which can be used at temperatures between -40ºC and +85ºC (+120ºC during short) records the temperatures with a 0,1º resolution.
Perfect for places with difficult access since it does not need maintenance or adjustments.
The cable is made of:
• 2 conductors plane cable with mounted hybrid circuits
• Packing material with relief traction (to secure the cable in case of fire)
• Integrated aluminium screen.
• External cover free of halogens and flame retardant.
It is supplied with different distances between sensors according the variant. The sensors inside the cable are separated with a distance of 1,2,3,4, or 5 m. Also it can be supplied made to order with other distance between specific sensors from 0,25 to 10m.
Other characteristics:
• Cable cover material free of halogens, flame retardant (conform to EN 60332-1-2, EN 60332-2-2 and IEC 60754-1)
• Approx. Diameter. 15 mm
• Weight per m 0,35 kg/m
AECS/SEC15-1 Sensors Cable every 1m
AECS/SEC15-2 Sensors Cable every 2m
AECS/SEC15-3 Sensor Cable every 3m
AECS/SEC15-4 Sensor Cable every 4m
AECS/SEC15-5 Sensor Cable every 5m
Connection with ferrule, 3 poles for CC15 line as a sensors cable complementary piece preassembled with connector SECcon.
Preassembled sensors cable with connector, 3 poles and terminal piece.
These modules monitor 1 or 2 cable zones. Powered with 24Vdc. Outputs for alarm& fault relays. Models with display for point identification alarm, in cabinet with IP66and zener barrier for installations in dangerous classified areas.
AEC-CJPH. Cable grommet
Metric adapter for the position of alarm point that converts almost any digital multimeter,in a counter of the alarm point position. If the cable was cut to locate and show witha reading the distance in feet (meters optionally), it helps to know the exact locationof the fire.
Metric adapter for the position of alarm point. Convert almost any digital multimeter,
in a counter of the alarm point position. If the cable was cut to locate
and show witha reading the distance in feet (meters optionally), it helps to
know the exact locationof the fire.
AEC-ELF. Fault localiser system
The linear heat detector is a thermal cable that consists of two conductors of twistedsteel, covered by a layer of heat sensitive polymer. Upon reaching the temperature,a contact between the two conductors is provoked, generating
an alarm signal. Available in various triggering temperatures.
As its main features we underline:
ALARM TEMPERATURE | REFERENCE |
68 ºC | AEC-EPC68. |
68 ºC cable clamp | AEC-EPC68M |
88 ºC | AEC-EPC88 |
88 ºC cable clamp | AEC-EPC88M |
105 ºC | AEC-EPC105 |
105 ºC cable clamp | AEC-EPC105M |
138ºC | AEC-EPC138 |
138ºC cable clamp | AEC-EPC138M |
180ºC | AEC-EPC180 |
180ºC cable clamp | AEC-EPC180M |
The linear heat detector is a thermal cable that consists of two conductors of twisted steel, covered by a layer of heat sensitive polymer. Upon reaching the temperature,a contact between the two conductors is provoked, generating an alarm signal. Available in various triggering temperatures.
As its main features we underline:
External covering out of polypropylene with environmental resistance, resistant to abrasion, UV protection, resistant to oils and high performance at elevated temperatures.
ALARM TEMPERATURE | REFERENCE |
68 ºC | AEC-EPR68 |
68 ºC Cable clamp | AEC-EPR68M |
88 ºC | AEC-EPR88 |
88ºC Cable clamp | AEC-EPR88 |