Referencia: AETS

TITANUS SUPER-SENS®

Specifically developed for applications with the highest detection standards. The system shows its special ability to detect pyrolysis gases, released during thermal processes,much before anyone can even speak of a “”fire””.

TITANUS SUPER·SENS® is a high sensitivity device for detecting smoke by takingair samples, for use in special applications such as telecommunication areas, CPD data centres and for monitoring clean-air rooms.

It offers numerous features, functions and operation options:

  • 3 alarm trigger points (warning, pre-alarm and alarm) with relays switched free ofvoltage
  • Fault Detector Relay.
  • 10-digit bar graph that keeps the user informed about the current smoke level presentin the monitored area.
  • Ethernet network connection, using an AET/ ITR network card.
  • Galvanic version for superior protection of areas with a corrosive atmosphere.

This variant ensures a longer life span in the presence of corrosive gases.

TITANUS SUPER·SENS® coverage goes far beyond the classification EN 54-20. The alarm’s sensitivity can be set, depending on the version, up to 600 times more sensitive than is necessary for reaching class A.

For that there will be pipe lengths of up to 200 m, regardless of what type of class, A,B or C is required, according to EN 54-20.

Specifications:

  • Energy supply: 24V CC (14 – 30)
  • Max. power consumption at rest: 245 mA
  • Max. power consumption of alarm: 320 mA
  • Max. nº of aspiration openings: 24
  • Maximum duct length: 200 m
  • Dimensions: 240 x 366 x 132 mm
  • Temperature interval: -20ºC to +60ºC
  • Humidity: from 10% to 95% without condensation.
  • Sensitivity of alarm response: 0.006% obs/m
  • Certificates: EN 54-20, classes A, B, C, nº 0786-CPD-20781
  • VdS Approval nº: G201035″
Referencia: AETT

Titanus Topsens

The TITANUS TOP·SENS® is a high sensitivity device for smoke detection by aspiration,with many operating features and options:

  • Connection to one or two detector modules. With just one device we can monitor two areas, or even double detection in the same area (by using the adapter in V mode)
  • 3 alarm trigger points (warning, pre-alarm and alarm) with relays switched free of voltage, for each detector module.
  • Fault Detector Relay.
  • 10-digit bar graph for each detector module, which keeps the user informed about the current smoke level that is present in the monitored area.
  • Ethernet network connection, by using AET / IT network card.
  • Connection to Aguilera Electronica´s algorithmic loop through the AE/SA-IT card.
  • Specific version for refrigerated zones, used in applications of up to -40ºC.
  • Silent version, with a noise level of 23 dB (A).

Specifications:

  • Energy supply: 24V CC (14 – 30 V CC)
  • Temperature interval: -20ºC to +60ºC
  • Class of protection: IP 20 (IP 52 is optional)
  • Dimensions: 200 x 292 x 113 mm
  • Humidity: from 10% to 95% without condensation
  • Dimensions: 200 x 292 x 113 mm
  • Certificates EN 54-20, classes A, B, C, number 0786-CPD-20685.
  • VdS Approval nº: G202064
REFERENCESENSITIVITY
AETT-500.5%
AETT-100.1%
AETT-010.015%
REFERENCESENSITIVITY
AETT-F500.5%
AETT-F100.1%
AETT-F010.015%
SENSITIVITY OF ALARM RESPONSE
REFERENCEMODULE 1MODULE 2
AETT-2-500.5%0.5%
AETT-2-10500.1%0.5%
AETT-2-100.1%0.1%
AETT-2-01500.015%0.5%
AETT-2-01100.015%0.1%
AETT-2-010.015%0.015%
SENSITIVITY OF ALARM RESPONSE
REFERENCEMODULE 1MODULE 2
AETT-F2-500.5%0.5%
AETT-F2-10500.1%0.5%
AETT-F2-100.1%0.1%
AETT-F2-01500.015%0.5%
AETT-F2-01100.015%0.1%
AETT-F2-010.015%0.015%
SENSITIVITY OF ALARM RESPONSE
REFERENCEMODULE 1MODULE 2
AETT-2-D50500.5%0.5%
AETT-2-D10500.1%0.5%
AETT-2-D01500.015%0.5%
AETT-2-D01100.015%0.1%