Referencia: AETP

Titanus Prosens

TITANUS PRO·SENS® has been developed for a broad range of applications.

The high modularity of the system offers an economical solution tailored to individual customer needs.
It offers the following options:

  • Connection to one or two detector modules. With just one device we can monitor two areas, or even double detection in the same area (by using the adapter in “Y” AET-P01109255 mode).
  • From 1 to 3 levels of alarm (warning, pre-alarm and alarm) with relays switched free of voltage, depending on the model, for each detector module.
  • Fault Detector Relay.
  • Ethernet network connection, using AET / IT network card (not for TP1 models).
  • Connection to Aguilera Electronica´s algorithmic loop through the card AE/SAIT.
  • Specific version for refrigerated zones, which can be used in applications up to -40ºC.
  • Silent version, with a noise level of 23 dB (A).

Specifications:

  • Energy supply: 24V CC (14 – 30)
  • Dimensions: 200x292x113 mm
  • Temperature interval: -20ºC to +60ºC
  • Humidity: from 10% to 95% without condensation.
  • Certificates EN 54-20, classes A, B, C, nº 0786-CPD-20685.
  • VdS Approval nº G 202064
    • Max. number of aspiration openings: 32
    • Max. duct length: 300 m
    • Consumption at rest: 200 mA
    • Maximum power consumption in alarm: 210 mA””

 

 

REFERENCESENSITIVITY
AETP1-500.5%
AETP1-100.1%
AETP1-010.015%
REFERENCESENSITIVITY
AETP1-F500.5%
AETP1-F100.1%
AETP1-F010.015%
  • Max. number of aspiration openings 64 (2 x 32)
  • Max. duct length: 560 m (2 x 280)
  • Consumption at rest: 220 mA
  • Maximum power consumption in alarm: 240 mA

 

REFERENCEMODULE 1MODULE 2
AETP1-2-500.5%0.5%
AETP1-2-10500.1%0.5%
AETP1-2-100.1%0.1%
AETP1-2-01500.15%0.5%
AETP1-2-01100.15%0.1%
AETP1-2-010.15%0.15%
REFERENCEMODULE 1MODULE 2
AETP1-F2-500.5%0.5%
AETP1-F2-10500.1%0.5%
AETP1-F2-1010.1%0.1%
AETP1-F2-01500.15%0.5%
AETP1-F2-01100.15%0.1%
AETP1-F2-010.15%0.15%

Titanus Prosens TP1 type – 2 detection modules for refrigerated environment

REFERENCEMODULE 1MODULE 2
AETP1-2-D50500.5%0.5%
AETP1-2-D10500.1%0.5%
AETP1-2-D01500.15%0.5%
AETP1-2-D01100.015%0.1%
  • Max. number of aspiration openings 32
  • Max. duct length: 300 m
  • Consumption at rest: 210 mA
  • Maximum power consumption in alarm: 220 mA
REFERENCESENSITIVITY
AETP4-500.5%
AETP4-100.1%
AETP4-010.015%
  • Max. number of aspiration openings: 64 (2 x 32)
  • Max. duct length: 560 m (2 x 280)
  • Consumption at rest: 240 mA
  • Maximum power consumption in alarm: 250 mA
REFERENCESENSITIVITY
ARTP4-F500.5%
ARTP4-F100.1%
ARTP4-F010.015%
  • Max. number of aspiration openings: 64 (2 x 32)
  • Max. duct length: 560 m (2 x 280)
  • Consumption at rest 240 mA
  • Maximum power consumption in alarm: 250 mA
SENSITIVITY OF ALARM RESPONSE
REFERENCEMODULE 1MODULE 2
AETP4-2-50.0.5%0.5%
AETP4-2-10500.1%0.5%
AETP4-2-100.1%0.1%
AETP4-2-01500.015%0.5%
AETP4-2-01100.015%0.1%
AETP4-2-010.015%0.015%
  • Max. number of aspiration openings: 32)
  • Max. duct length: 560 m (2 x 280)
  • Consumption at rest: 240 mA
  • Maximum power consumption in alarm: 250 mA
SENSITIVITY OF ALARM RESPONSE
REFERENCEMODULE 1MODULE 2
AETP4-F2-500.5%0.5%
AETP4-F2-10500.1%0.5%
AETP4-F2-100.1%0.1%
AETP4-F2-01500.015%0.5%
AETP4-F2-01100.015%0.1%
AETP4-F2-010.015%0.015%
  • Max. number of aspiration openings: 32
  • Max. duct length: 300 m
  • Consumption at rest: 210 mA
  • Maximum power consumption in alarm: 220 mA
REFERENCESENSITIVITY
AETP5-500.5%
AETP5-100.1%
AETP5-010.015%
  • Max. number of aspiration openings: 32
  • Max. duct length: 300 m
  • Consumption at rest: 210 mA
  • Maximum power consumption in alarm: 220 mA
REFERENCESENSITIVITY
AETP5-F500.5%
AETP5-F100.1%
AETP5-F010.015%
  • Max. number of aspiration openings: 64 (2 x 32)/li>
  • Max. duct length: 560 m (2 x 280)/li>
  • Consumption at rest: 240 mA/li>
  • Maximum power consumption in alarm: 250 mA
SENSITIVITY OF ALARM RESPONSE
REFERENCEMODULE 1MODULE 2
AETP5-2-500.5%0.5%
AETP5-2-10500.1%0.5%
AETP5-2-100.1%0.1%
AETP5-2-01500.015%0.5%
AETP5-2-01100.015%0.1%
AETP5-2-010.015%0.015%
  • Max. number of aspiration openings: 64 (2 x 32)
  • Max. duct length: 560 m (2 x 280)
  • Consumption at rest: 240 mA
  • Maximum power consumption in alarm: 250 mA
SENSITIVITY OF ALARM RESPONSE
REFERENCEMODULE 1MODULE 2
AETP5-2-D10500.1%0.5%
AETP5-2-D01500.015%0.5%
AETP5-2-D01100.015%0.1%
  • Max. number of aspiration openings: 64 (2 x 32)
  • Max. duct length: 560 m (2 x 280)
  • Consumption at rest: 240 mA
  • Maximum power consumption in alarm: 250 mA
SENSITIVITY OF ALARM RESPONSE
REFERENCEMODULE 1MODULE 2
AETP5-F2-50.0.5%0.5%
AETP5-F2-10500.1%0.5%
AETP5-F2-100.1%0.1%
AETP5-F2-01500.015%0.5%
AETP5-F2-01100.015%0.1%
AETP5-F2-010.015%0.015%