Referencia: AECS-RDU316

Remote Display

SCU 800 Remote display unit. In combination with up to 31 evaluation units, messages created are displayed and can be saved and chronologically selected (time and date). The cyclical memory and the clock in real time of the RDU 316 can stock and display up to 450 messages with time line.

• Operative temperature 0 °C to +60 °C
• Material ABS-FR
• Dimensions 110 × 140 × 60 mm
• Power Supply 10 – 36 V DC
• Current consumption with 24 V DC: Normal 40 mA; alarm 100 mA
• Type of protection IP 66

Referencia: AECS/DLIST

3 relay evaluation unit SCU800

The evaluation unit SCU 800 (Sensor Control Unit) is a central control device which supplies with voltage to a maximum of two sensor cables SEC 15, performs a cyclic enquiry of the connected sensors every 10 seconds, records the temperature values obtained and immediately evaluates it according to different criterions.
A fire alarm is activated if, at one measuring point, the temperature exceeds a line, or if the temperature increases over the time (differential performance).
Both alarm lines can be programmed up 64 configurable sectors.
The special evaluation algorithms minimize significantly the false alarms due to natural temperature changes.
The alarm is signalled both optically on the front of the device and through potential free contacts, for its electrical relaying to other computer and control systems or to a fire detection panel. Both the cable evaluation and the alarm signal are performed separately. The continuous enquiry of the sensors data can detect and signal immediate breakdown.
It has collective alarm relays (one for sensors cable) and one collective breakdown relay.
• Dimensions: 260 x 150 x 90 mm. Weight: 1,9 Kg
• Power Supply: 21 to 29 Vcc.
• Temperature: -10ºC to +60ºC
• Protection: IP65

Evaluation 16 relays Unit SCU800

The evaluation unit SCU 800 (Sensor Control Unit) is a central control device which supplies with voltage to a maximum of two sensor cables SEC 15, performs a cyclic enquiry of the connected sensors every 10 seconds, records the temperature values obtained and immediately evaluates it according to different criterions.
A fire alarm is activated if, at one measuring point, the temperature exceeds a line, or if the temperature increases over the time (differential performance).
Both alarm lines can be programmed up 64 configurable sectors.
The special evaluation algorithms minimize significantly the false alarms due to natural temperature changes.
The alarm is signalled both optically on the front of the device and through potential free contacts, for its electrical relaying to other computer and control systems or to a fire detection panel. Both the cable evaluation and the alarm signal are performed separately. The continuous enquiry of the sensors data can detect and signal immediate breakdown.
It has de 16 group relays which can be programed for the alarm signal, pre signal and breakdown per group.
• Dimensions: 260 x 150 x 90 mm. Weight: 2,3 Kg.
• Power Supply: 21 to 29 Vcc.
• Temperature: -10ºC to +60ºC
• Protection: IP65

Referencia: AECS/CBO15-ESD

Connection box CBO 5-ESD

Connection box is to connect 8 individual sensors to the bus or up to 4 individual sensors and a sensors cable run. For all the connections there are adjustment resistances which can be activated in shunt short lines if necessary

Working temperature: -35ºC to +60ºC (+80ºC in short time).
Protection: IP 66
Dimensions: 130x130x75mm

Ex-PROOF connection box

It provides power to a d-list temperature sensors cable and to 4 ESD individual sensors, or respectively to 8 individual sensors with UCM connection module. It is made with reinforced polyester with fibre glass.
Protection: IP65

Referencia: AECS/ESDEL

Rectangular external Sensor

A5 stainless steel sensor to use with d-LIST system, it is connected to the all system through a connection box AECS/CBO-ESD and, with it, to the evaluation and control unit. It is possible to consult up to 2×99 sensors maximum per unit.
Shape: rectangular 8mm
Temperature range: -55ºC to + 120ºC
AECS/ESDEL-01 (1m Connection cable)
AECS/ESDEL-05 (5m Connection cable)
AECS/ESDEL-10 (10m Connection cable)

Referencia: AECS/ESDRL

Circular external Sensor

A5 stainless Steel Sensor to use with d-LIST system, it is connected to the system directly in the bus through an AECS/CBO-ESD connection box and, with it, to the evaluation and control unit. It is possible to consult up to 2×99 sensors maximum per unit.
Shape: circular 8mm
Temperature range: -55ºC to + 120ºC
AECS/ESDRL-01 (1m connection cable)
AECS/ESDRL-05 (5m connection cable)
AECS/ESDRL-10 (10m connection cable)

Referencia: AECS/DLISTR835, AECS/DLISTR835A

Master LCON