Referencia: AE/CO-Z1M

1 zone central unit

Detectors developed and manufactured by AGUILERA ELECTRONICA, according tothe UNE 23300-84 norm and approved by the Ministry of Industry and Energy.

Designed for analyzing the concentration of carbon monoxide in garages and similar rooms, for starting the fan extractors when programmed values are reached, foractivating the evacuation sirens, if it comes to levels of high risk for the persons andfor returning the devices to the position of idle, when the concentration of carbonmonoxide drops to permissible values.
Equipped with:

  • Microprocessor control.
  • Auxiliary voltage output: 12VCC / 500mA.
  • A rotary selector of maximum concentration permitted by zone, with 10 positions allowing you to select between 25 and 250 ppm
  • A numerical display separate by zone that is permanently set at the maximum level of carbon monoxide being detected.
  • 3 detection levels and three relay outputs by zone Located in a metallic wall mounted cabinet.

Observation: when the installation has two sets of extractors by sector, the central units are programmed so that in the first level only one enters, and only if it is reallynecessary, enters the second set.

If with the two working sets functioning, still high levels of risk are reached (3rd level),then the central unit activates the evacuation systems.• With three detection levels and three relay outputs for maneuvers.

  • Capacity to control 10 detectors.
  • Cabinet measurements:245x330x120 mm.
  • Consumption at rest: 130 mA.